The most common HID lamps are metal halide (MH) and high pressure
sodium (HPS). Both feature long lamp life and can withstand temperature
extremes without significant loss of light output. Both sources require
time to start up and restrike. Kelvin temperature is 2,000K (a
yellowish-white color) for HPS and from 3,000 to 4,100K (a white to blue
white color) for MH. Other lamps are available to address specific global
markets. Lamp / ballast system performance may vary per manufacturer.
Certain metal halide lamps should be enclosed. Consult factory for
details.
| Lamp Type |
Nominal Lamp Wattage |
Initial Lumens |
Mean Lumens |
Lamp Life
12 hrs/start |
Color Rendering CRI |
Typical
Start-Up minutes3 |
Typical Restrike minutes |
Lamp Efficacy4 |
| Metal
Halide – Clear |
| |
175w |
14,400 |
12,000 |
10,000 |
65 |
2-5 |
10-15 |
69 |
|
250w |
22,000 |
17,000 |
10,000 |
65 |
2-5 |
10-15 |
68 |
|
400w |
36,000 |
25,000 |
20,000 |
65 |
2-5 |
10-15 |
63 |
|
1,000w |
110,000 |
88,000 |
12,000 |
65 |
2-5 |
10-15 |
88 |
| Metal
Halide – Coated |
| |
175w |
14,000 |
10,000 |
10,000 |
70 |
2-5 |
10-15 |
57 |
|
250w |
21,500 |
17,000 |
10,000 |
70 |
2-5 |
10-15 |
68 |
|
400w |
36,000 |
25,000 |
20,000 |
70 |
2-5 |
10-15 |
63 |
|
1,000w |
107,000 |
85,000 |
12,000 |
70 |
2-5 |
10-15 |
85 |
| Metal
Halide High output – Clear |
|
400w |
44,000 |
34,000 |
20,000 |
65 |
2-5 |
10-15 |
85 |
| Metal
Halide Pulse Ignition1 – Clear (requires special
ballast and ignitor) |
|
70w |
5,500 |
4,070 |
12,000 |
65 |
2 |
3-4 |
58 |
|
100w |
9,000 |
6,390 |
15,000 |
65 |
2 |
3-4 |
64 |
|
150 |
15,000 |
11,300 |
15,000 |
65 |
2 |
3-4 |
75 |
|
200 |
21,000 |
15,800 |
15,000 |
65 |
2 |
3-4 |
79 |
|
320 |
32,000 |
21,200 |
20,000 |
65 |
2 |
3-4 |
66 |
|
350 |
36,000 |
27,000 |
20,000 |
65 |
2 |
3-4 |
77 |
|
400 |
44,000 |
37,400 |
30,0002 |
65 |
2 |
3-4 |
94 |
| Metal
Halide Pulse Ignition1 – Coated (requires special
ballast and ignitor) |
|
150 |
14,250 |
10,300 |
15,000 |
70 |
2 |
3-4 |
69 |
|
200 |
20,000 |
14,400 |
15,000 |
70 |
2 |
3-4 |
72 |
|
350 |
34,500 |
24,900 |
20,000 |
70 |
2 |
3-4 |
71 |
|
400 |
42,000 |
35,200 |
30,0002 |
70 |
2 |
3-4 |
88 |
| Metal
Halide Reg-lag – Clear (requires reg-lag ballast and ignitor) |
|
250 |
23,750 |
19,000 |
20,0002 |
65 |
2 |
3-4 |
76 |
|
400 |
44,000 |
37,400 |
30,0002 |
65 |
2 |
3-4 |
94 |
| Metal
Halide Reg-lag – Coated (requires reg-lag ballast and ignitor) |
|
250 |
22,600 |
17,500 |
20,0002 |
70 |
2 |
3-4 |
70 |
|
400 |
42,000 |
35,200 |
30,0002 |
70 |
2 |
3-4 |
88 |
| High
Pressure Sodium – Clear |
| |
70 |
6,400 |
5,440 |
24,000 |
20 – 25 |
3-4 |
1-2 |
78 |
|
100 |
9,500 |
8,550 |
24,000 |
20 – 25 |
3-4 |
1-2 |
86 |
|
150 |
16,000 |
14,400 |
24,000 |
20 – 25 |
3-4 |
1-2 |
96 |
|
200 |
22,000 |
19,600 |
24,000 |
20 – 25 |
3-4 |
1-2 |
98 |
|
250 |
28,000 |
25,200 |
24,000 |
20 – 25 |
3-4 |
1-2 |
101 |
|
310 |
37,000 |
33,300 |
24,000 |
20 – 25 |
3-4 |
1-2 |
107 |
|
350 |
46,500 |
44,000 |
24,000 |
20 – 25 |
3-4 |
1-2 |
126 |
|
400 |
50,000 |
45,000 |
24,000 |
20 – 25 |
3-4 |
1-2 |
113 |
|
1,000 |
140,000 |
126,000 |
24,000 |
20 – 25 |
3-4 |
1-2 |
126 |
| High
Pressure Sodium – Coated |
| |
70 |
5,950 |
5,058 |
24,000 |
20 – 25 |
3-4 |
1-2 |
72 |
|
100 |
8,800 |
7,920 |
24,000 |
20 – 25 |
3-4 |
1-2 |
79 |
|
150 |
15,000 |
13,500 |
24,000 |
20 – 25 |
3-4 |
1-2 |
90 |
|
250 |
26,000 |
23,400 |
24,000 |
20 – 25 |
3-4 |
1-2 |
94 |
|
400 |
47,500 |
42,750 |
24,000 |
20 – 25 |
3-4 |
1-2 |
107 |
- High lumen, pulse ignition lamp/ballast system with a capacitor and
internal ignitor
- 120 hrs per start
- Time to reach 90% of full light output
- Mean lumens per watt
HID
Ballast Data
|
| |
| Ballast type |
Input watts |
Ballast regulation
(line voltage / lamp wattage) |
Ballast losses |
Avg. Dip Tolerance % |
Voltages1 |
| Metal Halide |
| 400w CWA |
458 |
±
10% / ± 10% |
Medium |
50% |
120,208,240, 277,347,480 |
| 400w SCWA2 |
456 |
±
10% / ± 10% |
Medium |
50% |
120,208,240, 277,347,480 |
| 350w SCWA2 |
400 |
±
10% / ± 10% |
Medium |
40% |
120,208,240, 277,347,480 |
| 400w LLR |
425 |
±
5% / ± 9% |
Low |
25% |
277 |
| 400w LLRPSL2 |
425 |
±
5% / ± 9% |
Low |
25% |
277 |
| 350w LLRPSL2 |
375 |
±
5% / ± 9% |
Low |
25% |
277 |
| 400w RLB |
465 |
±
10% / ± 7% |
High |
45-50% |
120, 208 240, 277,
347,480 |
| 250w RLB |
298 |
±
10% / +5%, -7% |
High |
30% |
120,208 240, 277, 347,480 |
| 175w RLB |
220 |
±
10% / +4%, -6% |
High |
30% |
120, 208,240,277, 347,480 |
| High Pressure Sodium |
| 400w CWA |
457 |
±
10% / ± 10% |
Med. to High |
40% |
120,208,240,277,347,480 |
| 250w CWA |
295 |
±
10% / ± 10% |
Med. to High |
30% |
120,208,240,277,347,480 |
| 400w MRB |
480 |
±
10% / ± 3% |
High |
45% |
120,208,240,277,480 |
1. For international business, 50 hertz equipment and other
voltages are available, consult factory
2. For use with pulse ignition lamps
Temperature Effect on HID Ballast/Component Life
Temperature has a tremendous effect on the life expectancy of a ballast and its related
components. Therefore, it is important not to exceed the maximum ambient rating of the
fixture. Operating a fixture in environments that are cooler than its rated ambient
temperature will greatly increase ballast life. It is generally accepted that for every 13° C drop
below the fixture's rated ambient temperature, the life of the ballast doubles. Capacitor
life is doubled when ambient temperatures drop 10° C below rating.

|