LITHONIA CONTROLS
FLUORESCENT DIMMING GUIDE
|
Based on
ballast manufacturer product data available 4-27-01; check with the listed
ballast manufacturer for up-to-date
information on valid lamp types for each ballast |
|
|
|
|
|
|
|
|
|
|
|
|
Ballast: |
Advance |
Lutron |
ESI |
Sylvania |
MagneTek |
Advance |
Lutron |
Lutron |
Lutron |
|
|
Mark VII |
ECO-10 |
SuperDim |
Helios |
Ballastar |
Mark X |
Tu-Wire |
ECO-10 |
Hi-Lume |
|
Control Type |
Four Wire |
Four Wire |
Four Wire |
Four Wire |
Four Wire |
Two Wire
Line Voltage |
Two Wire
Line Voltage |
Three Wire
Line Voltage |
Three Wire
Line Voltage |
|
Low End
Dimming Range 1 |
5% |
10% |
1% |
1% |
5% |
5% |
5% |
10% |
1% |
|
Ballast
Nomenclature |
RZT/VZT |
TVE |
DIM-D,
DIM-10 |
(PHO-) DIM |
V5 |
REZ/VEZ |
2W |
ECO |
FDB |
|
Lithonia
Nomenclature |
ADZT |
TVE10 |
ESIDD, ESIDA |
OSDIM |
TUBV5 |
ADEZ |
|
ECO10 |
DMHL |
|
Lamp Type : |
The number
of lamps that can be operated by each ballast is indicated below |
|
|
|
|
F13 Quad Tube |
~ |
~ |
1,2 |
~ |
~ |
~ |
~ |
~ |
~ |
|
F18 Quad Tube |
~ |
~ |
1,2 |
~ |
~ |
~ |
2 |
~ |
1,2 |
|
F26 Quad Tube |
~ |
~ |
1,2 |
~ |
~ |
2 |
1,2 |
~ |
1,2 |
|
F26 Triple
Tube |
~ |
~ |
1 |
~ |
~ |
1 |
~ |
~ |
~ |
|
F32 Triple
Tube |
~ |
1 |
1 |
~ |
~ |
1 |
1,2 |
~ |
1 |
|
F42 Triple
Tube |
~ |
~ |
1 |
~ |
~ |
1 |
~ |
~ |
~ |
|
F39 Biax T5 |
~ |
~ |
~ |
~ |
~ |
~ |
~ |
1,2,3 |
1,2,3 |
|
F40 Biax T5 |
1,2 |
2,3 |
~ |
~ |
~ |
1,2 |
~ |
1,2,3 |
1,2,3 |
|
F50 Biax T5 |
~ |
~ |
~ |
~ |
~ |
~ |
~ |
1,2 |
1,2 |
|
F28 T5 |
~ |
~ |
1,2 |
~ |
~ |
~ |
~ |
~ |
~ |
|
F54 T5 HO |
~ |
~ |
1 |
1,2 |
~ |
~ |
~ |
~ |
1,2 |
|
F17 T8 |
~ |
1 |
1,2 |
1,2,3,4 |
~ |
~ |
~ |
1,2,3 |
1,2,3 |
|
F25 T8 |
1,2,3 |
1 |
1,2 |
1,2,3,4 |
1 |
1,2,3 |
~ |
1,2 |
1,2,3 |
|
F32 T8 |
1,2,3 |
1,2,3 |
1,2 |
1,2,3,4 |
1,2,3,4 |
1,2,3 |
1,2 |
1,2,3 |
1,2,3 |
|
F40 T8 |
~ |
~ |
~ |
~ |
~ |
~ |
~ |
~ |
1,2 |
|
F30 T12 |
~ |
~ |
~ |
~ |
~ |
~ |
~ |
~ |
1,2 |
|
F40 T12 |
~ |
~ |
~ |
~ |
~ |
~ |
~ |
~ |
1,2 |
|
|
|
|
|
|
|
|
|
|
|
|
Wallbox
Dimmers |
|
|
|
|
|
|
|
|
|
|
SLD Series |
SLD LVBC 2 |
SLD LVBC 2 |
SLD LVBC 2 |
SLD LVBC 2 |
SLD LVBC 2 |
SLD FD 3 |
SLD FD 3 |
SLD FD |
SLD FD |
|
DSD Series |
N/A |
N/A |
N/A |
N/A |
N/A |
DSD ADEZ |
DSD ADEZ |
N/A |
N/A |
|
Equinox |
LEQ BC |
LEQ BC |
LEQ BC |
LEQ BC |
LEQ BC |
N/A |
N/A |
N/A |
N/A |
|
Digital
Equinox 4 |
DEQ BC, LC 2 |
DEQ BC, LC 2 |
DEQ BC, LC 2 |
DEQ BC, LC 2 |
DEQ BC, LC 2 |
N/A |
N/A |
N/A |
N/A |
|
|
|
|
|
|
|
|
|
|
|
|
Architectural
Systems |
|
|
|
|
|
|
|
|
|
|
Synergy
Dimmer Module |
Yes 5 |
Yes 5 |
Yes 5 |
Yes 5 |
Yes 5 |
Yes |
Yes |
Yes |
Yes |
|
MiniPac Pack
Types |
FC, UF |
FC, UF |
FC, UF |
FC, UF |
FC, UF |
UX, UF |
UX, UF |
UF |
UF |
|
Sequel IDC 6 |
Yes 5 |
Yes 5 |
Yes 5 |
Yes 5 |
Yes 5 |
Yes |
Yes |
Yes7 |
Yes7 |
|
|
|
|
|
|
|
|
|
|
|
|
Remote Dimmer
Modules |
|
|
|
|
|
|
|
|
|
|
120V |
RDMFC |
RDMFC |
RDMFC |
RDMFC |
RDMFC |
RDM |
RDM |
RDM |
RDM |
|
277V |
RDMFC |
RDMFC |
RDMFC |
RDMFC |
RDMFC |
RDMFM |
RDMFM |
RDMFM |
RDMFM |
|
|
|
|
|
|
|
|
|
|
|
|
Notes: |
|
|
|
|
|
|
|
|
|
|
1. Minimum low
end for each ballast type. Refer to the ballast manufacturer's information
for specific lamp types. |
|
|
|
2. Requires
LPCS power control station. |
|
|
|
|
|
|
|
|
3. Requires
RDM Remote dimmer module |
|
|
|
|
|
|
|
|
4. All Digital
Equinox products may operate stand-alone or as an integrated part of the
Synergy Lighting Control System. |
|
|
5. Requires
RDMFC remote dimmer module per circuit. |
|
|
|
|
|
|
|
6. 120V only
without the use of and RDM or MiniPac |
|
|
|
|
|
|
|
7. Two ballast
minimum loading |
|
|
|
|
|
|
|
|
|
4/27/01;