The most common HID lamps are metal halide (MH) and high pressure sodium (HPS). Both feature long lamp life and can withstand temperature extremes without significant loss of light output. Both sources require time to start up and restrike. Kelvin temperature is 2,000K (a yellowish-white color) for HPS and from 3,000 to 4,100K (a white to blue white color) for MH. Other lamps are available to address specific global markets. Lamp / ballast system performance may vary per manufacturer. Certain metal halide lamps should be enclosed. Consult factory for details.
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Ballast type | Input watts |
Ballast regulation |
Ballast losses |
Avg. Dip Tolerance % |
Voltages1 |
| Metal Halide | |||||
| 400w CWA | 458 |
± 10% / ± 10% |
Medium |
50% |
120,208,240, 277,347,480 |
| 400w SCWA2 | 456 |
± 10% / ± 10% |
Medium |
50% |
120,208,240, 277,347,480 |
| 350w SCWA2 | 400 |
± 10% / ± 10% |
Medium |
40% |
120,208,240, 277,347,480 |
| 400w LLR | 425 |
± 5% / ± 9% |
Low |
25% |
277 |
| 400w LLRPSL2 | 425 |
± 5% / ± 9% |
Low |
25% |
277 |
| 350w LLRPSL2 | 375 |
± 5% / ± 9% |
Low |
25% |
277 |
| 400w RLB | 465 |
± 10% / ± 7% |
High |
45-50% |
120, 208 240, 277, 347,480 |
| 250w RLB | 298 |
± 10% / +5%, -7% |
High |
30% |
120,208 240, 277, 347,480 |
| 175w RLB | 220 |
± 10% / +4%, -6% |
High |
30% |
120, 208,240,277, 347,480 |
| High Pressure Sodium | |||||
| 400w CWA | 457 |
± 10% / ± 10% |
Med. to High |
40% |
120,208,240,277,347,480 |
| 250w CWA | 295 |
± 10% / ± 10% |
Med. to High |
30% |
120,208,240,277,347,480 |
| 400w MRB | 480 |
± 10% / ± 3% |
High |
45% |
120,208,240,277,480 |
1. For international business, 50 hertz equipment and other
voltages are available, consult factory
2. For use with pulse ignition lamps
Temperature Effect on HID Ballast/Component Life
Temperature has a tremendous effect on the life expectancy of a ballast and its related components. Therefore, it is important not to exceed the maximum ambient rating of the fixture. Operating a fixture in environments that are cooler than its rated ambient temperature will greatly increase ballast life. It is generally accepted that for every 13° C drop below the fixture's rated ambient temperature, the life of the ballast doubles. Capacitor life is doubled when ambient temperatures drop 10° C below rating.